kVA to Amps Chart
Every rating from 0.5 to 3,000 kVA converted at the six voltages that cover most real work. For a value the table skips — an unusual rating or a voltage it does not list — the calculator directly below the chart gives the same math instantly.
The full kVA to amps chart
Amps are rounded to two decimal places, the same rounding the calculators use. For breaker and cable decisions, apply your code's rules on top of these figures — the chart gives the load, not the protection.
| kVA | 120V · single-phase | 240V · single-phase | 208V · three-phase | 400V · three-phase | 415V · three-phase | 480V · three-phase |
|---|---|---|---|---|---|---|
| 0.5 | 4.17 | 2.08 | 1.39 | 0.72 | 0.70 | 0.60 |
| 1 | 8.33 | 4.17 | 2.78 | 1.44 | 1.39 | 1.20 |
| 1.5 | 12.50 | 6.25 | 4.16 | 2.17 | 2.09 | 1.80 |
| 2 | 16.67 | 8.33 | 5.55 | 2.89 | 2.78 | 2.41 |
| 3 | 25.00 | 12.50 | 8.33 | 4.33 | 4.17 | 3.61 |
| 5 | 41.67 | 20.83 | 13.88 | 7.22 | 6.96 | 6.01 |
| 6 | 50.00 | 25.00 | 16.65 | 8.66 | 8.35 | 7.22 |
| 7.5 | 62.50 | 31.25 | 20.82 | 10.83 | 10.43 | 9.02 |
| 9 | 75.00 | 37.50 | 24.98 | 12.99 | 12.52 | 10.83 |
| 10 | 83.33 | 41.67 | 27.76 | 14.43 | 13.91 | 12.03 |
| 15 | 125.00 | 62.50 | 41.64 | 21.65 | 20.87 | 18.04 |
| 20 | 166.67 | 83.33 | 55.51 | 28.87 | 27.82 | 24.06 |
| 25 | 208.33 | 104.17 | 69.39 | 36.08 | 34.78 | 30.07 |
| 30 | 250.00 | 125.00 | 83.27 | 43.30 | 41.74 | 36.08 |
| 40 | 333.33 | 166.67 | 111.03 | 57.74 | 55.65 | 48.11 |
| 45 | 375.00 | 187.50 | 124.91 | 64.95 | 62.60 | 54.13 |
| 50 | 416.67 | 208.33 | 138.79 | 72.17 | 69.56 | 60.14 |
| 60 | 500.00 | 250.00 | 166.54 | 86.60 | 83.47 | 72.17 |
| 62.5 | 520.83 | 260.42 | 173.48 | 90.21 | 86.95 | 75.18 |
| 75 | 625.00 | 312.50 | 208.18 | 108.25 | 104.34 | 90.21 |
| 100 | 833.33 | 416.67 | 277.57 | 144.34 | 139.12 | 120.28 |
| 112.5 | 937.50 | 468.75 | 312.27 | 162.38 | 156.51 | 135.32 |
| 125 | 1,041.67 | 520.83 | 346.97 | 180.42 | 173.90 | 150.35 |
| 150 | 1,250.00 | 625.00 | 416.36 | 216.51 | 208.68 | 180.42 |
| 167 | 1,391.67 | 695.83 | 463.55 | 241.04 | 232.33 | 200.87 |
| 200 | 1,666.67 | 833.33 | 555.14 | 288.68 | 278.24 | 240.56 |
| 225 | 1,875.00 | 937.50 | 624.54 | 324.76 | 313.02 | 270.63 |
| 250 | 2,083.33 | 1,041.67 | 693.93 | 360.84 | 347.80 | 300.70 |
| 300 | 2,500.00 | 1,250.00 | 832.72 | 433.01 | 417.36 | 360.84 |
| 400 | 3,333.33 | 1,666.67 | 1,110.29 | 577.35 | 556.48 | 481.13 |
| 500 | 4,166.67 | 2,083.33 | 1,387.86 | 721.69 | 695.60 | 601.41 |
| 550 | 4,583.33 | 2,291.67 | 1,526.65 | 793.86 | 765.16 | 661.55 |
| 630 | 5,250.00 | 2,625.00 | 1,748.71 | 909.33 | 876.46 | 757.77 |
| 750 | 6,250.00 | 3,125.00 | 2,081.79 | 1,082.53 | 1,043.40 | 902.11 |
| 800 | 6,666.67 | 3,333.33 | 2,220.58 | 1,154.70 | 1,112.96 | 962.25 |
| 1,000 | 8,333.33 | 4,166.67 | 2,775.72 | 1,443.38 | 1,391.21 | 1,202.81 |
| 1,250 | 10,416.67 | 5,208.33 | 3,469.65 | 1,804.22 | 1,739.01 | 1,503.52 |
| 1,500 | 12,500.00 | 6,250.00 | 4,163.58 | 2,165.06 | 2,086.81 | 1,804.22 |
| 2,000 | 16,666.67 | 8,333.33 | 5,551.44 | 2,886.75 | 2,782.41 | 2,405.63 |
| 2,500 | 20,833.33 | 10,416.67 | 6,939.31 | 3,608.44 | 3,478.01 | 3,007.03 |
| 3,000 | 25,000.00 | 12,500.00 | 8,327.17 | 4,330.13 | 4,173.62 | 3,608.44 |
Balanced three-phase load, line-to-line voltage. Change any value and the result updates instantly.
Written-out answers for the most-searched values
The nine ratings people look up most, spelled out at every chart voltage — handy if you arrived from a search for one specific conversion.
1 kVA in amps
Single-phase, a 1 kVA load draws 4.17 A at 240 V — and 8.33 A at 120 V, which is why small ratings belong on the higher voltage where one exists. Three-phase, the same 1 kVA is 2.78 A at 208 V, 1.44 A at 400 V, 1.39 A at 415 V and 1.20 A at 480 V.
5 kVA in amps
Single-phase, a 5 kVA load draws 20.83 A at 240 V — and 41.67 A at 120 V, which is why small ratings belong on the higher voltage where one exists. Three-phase, the same 5 kVA is 13.88 A at 208 V, 7.22 A at 400 V, 6.96 A at 415 V and 6.01 A at 480 V.
10 kVA in amps
Single-phase, a 10 kVA load draws 41.67 A at 240 V — and 83.33 A at 120 V, which is why small ratings belong on the higher voltage where one exists. Three-phase, the same 10 kVA is 27.76 A at 208 V, 14.43 A at 400 V, 13.91 A at 415 V and 12.03 A at 480 V.
15 kVA in amps
Single-phase, a 15 kVA load draws 62.50 A at 240 V — and 125.00 A at 120 V, which is why small ratings belong on the higher voltage where one exists. Three-phase, the same 15 kVA is 41.64 A at 208 V, 21.65 A at 400 V, 20.87 A at 415 V and 18.04 A at 480 V.
25 kVA in amps
Single-phase, a 25 kVA load draws 104.17 A at 240 V — and 208.33 A at 120 V, which is why small ratings belong on the higher voltage where one exists. Three-phase, the same 25 kVA is 69.39 A at 208 V, 36.08 A at 400 V, 34.78 A at 415 V and 30.07 A at 480 V.
50 kVA in amps
Single-phase, a 50 kVA load draws 208.33 A at 240 V — and 416.67 A at 120 V, which is why small ratings belong on the higher voltage where one exists. Three-phase, the same 50 kVA is 138.79 A at 208 V, 72.17 A at 400 V, 69.56 A at 415 V and 60.14 A at 480 V.
100 kVA in amps
Single-phase, a 100 kVA load draws 416.67 A at 240 V — and 833.33 A at 120 V, which is why small ratings belong on the higher voltage where one exists. Three-phase, the same 100 kVA is 277.57 A at 208 V, 144.34 A at 400 V, 139.12 A at 415 V and 120.28 A at 480 V.
500 kVA in amps
Single-phase, a 500 kVA load draws 2,083.33 A at 240 V — and 4,166.67 A at 120 V, which is why small ratings belong on the higher voltage where one exists. Three-phase, the same 500 kVA is 1,387.86 A at 208 V, 721.69 A at 400 V, 695.60 A at 415 V and 601.41 A at 480 V.
1,000 kVA in amps
Single-phase, a 1,000 kVA load draws 4,166.67 A at 240 V — and 8,333.33 A at 120 V, which is why small ratings belong on the higher voltage where one exists. Three-phase, the same 1,000 kVA is 2,775.72 A at 208 V, 1,443.38 A at 400 V, 1,391.21 A at 415 V and 1,202.81 A at 480 V.
How the chart is built
Nothing in the table is typed by hand. Every cell is computed from the same two identities the calculators use — amps = kVA × 1000 ÷ volts single-phase, and amps = kVA × 1000 ÷ (√3 × volts) three-phase — so the chart and the tools can never disagree. The ratings list combines standard generator and transformer sizes (including 62.5, 112.5 and 167 kVA) with the in-between values people actually search for, up to 3,000 kVA. The methodology page documents the rounding rules. For a rating in a machine-specific frame, the generator calculator and the transformer calculator read the same figures with their duty and protection context attached.
A note on the 120V column
Large ratings at 120 V produce currents no real 120 V service would carry — 3,000 kVA at 120 V is 25,000.00 A on paper. The column is complete for consistency and for the small ratings where 120 V is real (UPS units, control power, small appliances), not a suggestion that such services exist at the top of the table.
Frequently asked questions
How do I read this kVA to amps chart?
Find your kVA in the first column, then read across to the column that matches your voltage and phase. A 50 kVA row, for example, gives 208.33 A at 240 V single-phase and 72.17 A at 400 V three-phase. If your exact rating or voltage is not listed, the calculator below the chart on this page computes it directly.
Why does the same kVA give different amps in every column?
Because current is power divided by voltage: the same apparent power at a lower voltage needs proportionally more current. That is why the 120 V column is exactly double the 240 V column, and why three-phase columns are lower than single-phase ones would be at the same voltage — the √3 in the three-phase formula shares the power across three conductors.
Is this chart valid for both generators and transformers?
Yes. Full-load amps depend only on the kVA rating and the voltage, not on the machine producing or passing the power. Generator and transformer plates both state kVA for exactly this reason. What differs between machines is the duty and protection around that current, which the dedicated generator and transformer pages cover.
What if my voltage is not in the chart — 380V or 600V?
The chart covers the six most common voltages. For anything else, use the calculator below the chart: the conversion is a division, not a lookup, so 380 V, 600 V and any other supply voltage all work in the tool. Example: 100 kVA at 600 V three-phase is 96.23 A.
Can I print this chart for the workshop wall?
Yes — that is what the Print this chart button above the table is for. The print version hides the site navigation and the calculator and lays the full table out in clean black and white, so it stays readable pinned next to a panel or inside a site office.
Sources and references
The chart is generated from the standards-based identities below; voltages follow the IEC and North American standards listed here.
- NFPA 70 — National Electrical Code (NEC) — the code electricians size conductors and protection against
- IEEE Std 141 — Recommended Practice for Electric Power Distribution (Red Book) — apparent power and load-current practice for industrial and commercial systems
- IEC 60038 — Standard Voltages — the standard voltage levels (120, 208, 240, 400, 480 V) used across this site
- NIST — SI unit of electric current (the ampere) — the definition of the ampere behind every result